Chapter 5 Programming Conversion Errors (PCE) Messages
68 Publication 1756-RM085G-EN-P - November 2023
The structure of FOR/NXT/BRK statements has changed in the Logix
architecture. In the PLC-5 processor, the FOR and NXT instruction enclosed
a section of code that was to be iterated multiple times, while the BRK
instruction allowed a way to break out of the repeating code.
In the RSLogix architecture, the FOR instruction calls a given routine a
specific number of times, so a NXT instruction is not needed. The BRK
instruction works in a similar fashion as in the PLC-5 processor. Because
this architecture change is significant, you will probably have to consider
restructuring your logic.
Each time FOR/NXT/BRK instructions are encountered.
AGA instruction not supported.
Each time a AGA instruction is found.
Each time a CIR or CIO instruction is found.
Source and destination types differ.
When source and destination types differ in a COP instruction.
DFA instruction not supported
Each time a DFA instruction is found.
ERI/ERO instruction not supported.
Each time a ERI or ERO instruction is found.
IDI/IDO instruction not supported.
Each time a IDI or IDO instruction is found.
IIN/IOT instruction not supported.
Each time a IIN or IOT instruction is found.
SFC routines aren’t migrated.
Each time a SFR or EOT instruction is found.
129 Online edit instructions are not supported. Each time a SDS, SIZ or SRZ instruction is found.
130 User Interrupt instructions not supported. Each time a UID, UIE or UIF instruction is found.
DDV instruction not supported.
Each time a DDV instruction is found.
High Speed Counter instructions not supported.
Each time a HSC/HSD/HSE/ SL or RHC/RAC/TDF instruction is found.
I/O Interrupt Enable/Disable instructions not supported.
Each time a IID or IIE instruction is found.
IIM/IOM instruction not supported.
Each time a IIM or IOM instruction is found.
135 INT instruction not supported. Each time a INT instruction is found.
REF instruction not supported.
Each time a REF instruction (in SLC) is found.
RPI instruction not supported.
Each time a RPI instruction is found.
Selectable Timed Interrupt instructions not supported.
Each time a STD/STE or STS instruction is found.
SUS instruction not supported.
Each time a SUS instruction is found.
141 RMP instruction not supported. Each time a RMP instruction is found.
142 RPC instruction not supported. Each time a RPC instruction is found.
143 SVC instruction not supported. Each time a SVC instruction is found.
SWP instruction not supported.
Each time a SWP instruction is found.
SQC instruction not supported.
Each time a SQC instruction is found.
INV instruction not supported.
Each time a INV instruction is found.
DCD/ENC instruction not supported.
Each time a DCD or ENC instruction is found.
148 The CEM, DEM, or EEM instruction has been converted. However, the
conversion needs to be validated. These instructions have many parameters
that cannot be directly converted and require review.
Each time a CEM, DEM or EEM instruction is found.
149 Modbus messaging is not supported in Logix Designer software. If MSG instruction is configured for Modbus.
MSG instruction and associated MESSAGE tag need to be manually verified.
Each time a MSG instruction is found.
151
: Status files do not exist in Logix Designer software.
However this status file value is handled through the StatusFile routine.
S file type indexes that can be directly converted to functionality in Logix
Designer software.
152 Logix Designer software has a different fault handling mechanism than the
PLC-5/SLC. This fault routine will not be called.
Start of identified legacy processor fault routine.
153 This PII/DII routine is not used by Logix Designer software. Start of identified legacy processor PII/DII routine.